Section 8
Frequency protection
8.2.3
8.2.4
8.2.5
Table 142:
SAPTOF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
tDelay
0.000 - 60.000
8.2.6
196

Function block

SAPTOF (81)
V3P*
TRIP
BLOCK
BFI
BLKDMAGN
ANSI09000280-1-en.vsd
ANSI09000280 V1 EN
Figure 81:
SAPTOF (81) function block

Signals

Table 140:
SAPTOF (81) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 141:
SAPTOF (81) Output signals
Name
Type
TRIP
BOOLEAN
BFI
BOOLEAN
BLKDMAGN
BOOLEAN

Settings

Unit
Step
-
-
Hz
0.01
s
0.001
Monitored data
Table 143:
SAPTOF (81) Monitored data
Name
Type
FREQ
REAL
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
Description
Common trip signal
General pickup signal
Measurement blocked due to low amplitude
Default
Description
Disabled
Operation Disable / Enable
51.20
Frequency set value
0.200
Operate time delay
Values (Range)
Unit
-
Hz
1MRK 511 287-UUS A
Description
Measured frequency