1MRK 511 287-UUS A
11.9.5
Table 335:
TEIGGIO Group settings (basic)
Name
Values (Range)
Operation
0 - 1
tWarning
1.00 - 999999.99
tAlarm
1.00 - 999999.99
11.9.6
Technical manual
Table 334:
TEIGGIO Output signals
Name
Type
WARNING
BOOLEAN
ALARM
BOOLEAN
OVERFLOW
BOOLEAN
ACCTIME
REAL

Settings

Unit
Step
-
1
s
0.01
s
0.01
Operation principle
The elapsed time integrator (TEIGGIO) provides
time integration, accumulating the elapsed time when a given binary signal has been
high.
blocking and reset.
supervision of limit transgression and overflow.
retaining of the integrated value if any warning, alarm or overflow occurs.
Figure
196
describes the simplified logic of the function where the block "Time
Integration" covers the logics for the first two items listed above while the block
"Transgression Supervision Plus Retain" contains the logics for the last two.
Description
Indicator of the integrated time has reached the warning
limit
Indicator of the integrated time has reached the alarm
limit
Indicator of the integrated time has reached the overflow
limit
Integrated elapsed time in seconds
Default
Description
1
Disable/Enable Operation
600.00
Time limit for warning supervision
1200.00
Time limit for alarm supervision
Section 11
Logic
415