It is always possible to make a substitution, independently of the position
indication and the status information of the I/O board. When substitution
is enabled, the position values are blocked for updating . The substituted
values are stored in a non-volatile memory.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse
is sent. tIntermediate defines the maximum allowed time for intermediate position.
Figure
121
explains these two timers during the execute phase.
Close pulse duration
t1
tStartMove
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command
can have different pulse lengths. The pulses can also be set to be adaptive with the
configuration parameter AdaptivePulse. Figure
output pulse. The AdaptivePulse parameter will have affect on both execute output pulses.
t2
tIntermediate
en05000097.vsd
122
shows the principle of the execute
1MRK 511 287-UUS A
AdaptivePulse = TRUE
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set