Signals - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 10
Control
10.11.3
10.11.4
Table 247:
I103IEDCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
10.12
10.12.1
360

Signals

Table 245:
I103IEDCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 246:
I103IEDCMD Output signals
Name
Type
19-LEDRS
BOOLEAN
23-GRP1
BOOLEAN
24-GRP2
BOOLEAN
25-GRP3
BOOLEAN
26-GRP4
BOOLEAN
Settings
Unit
Step
-
1
Function commands user defined for IEC 60870-5-103
I103USRCMD
Functionality
I103USRCMD is a command block in control direction with user defined output signals.
These function blocks include the FunctionType parameter for each block in the private
range, and the Information number parameter for each output signal.
Default
Description
0
Block of commands
Description
Information number 19, reset LEDs
Information number 23, activate setting group 1
Information number 24, activate setting group 2
Information number 25, activate setting group 3
Information number 26, activate setting group 4
Default
Description
255
Function type (1-255)
1MRK 511 287-UUS A
Technical manual