Signals; Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 9
Secondary system supervision
9.1.4
9.1.5
Table 151:
CCSRDIF (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IMinOp
5 - 200
Table 152:
CCSRDIF (87) Group settings (advanced)
Name
Values (Range)
Pickup_Block
5 - 500
Table 153:
CCSRDIF (87) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
204

Signals

Table 149:
CCSRDIF (87) Input signals
Name
Type
I3P
GROUP
SIGNAL
IREF
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 150:
CCSRDIF (87) Output signals
Name
Type
FAIL
BOOLEAN
ALARM
BOOLEAN

Settings

Unit
Step
-
-
%IB
1
Unit
Step
%IB
1
Unit
Step
-
1
Default
Description
-
Three phase group signal for current inputs
-
Group signal for current reference
0
Block of function
Description
Detection of current circuit failure
Alarm for current circuit failure
Default
Description
Disabled
Disable/Enable Operation
20
Minimum operate current differential pickup in
% of IBase
Default
Description
150
Block of the function at high phase current, in %
of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 511 287-UUS A
Technical manual