The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number of
operations has reached a predefined value. For proper functioning of the circuit breaker,
it is essential to monitor the circuit breaker operation, spring charge indication, breaker
wear, travel time, number of operation cycles and accumulated energy. The energy is
calculated from the measured input currents as a sum of I
when the calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
•
breaker open and close travel time
•
spring charging time
•
number of breaker operations
•
Y
accumulated I
t per phase with alarm and lockout
•
remaining breaker life per phase
•
breaker inactivity
Function block
SSCBR
I3P*
TRVTOAL
BLOCK
TRVTCAL
BLK_ALM
SPRCHRAL
POSOPEN
OPRALM
POSCLOSE
OPRLOALM
ALMPRES
IACCALM
LOPRES
IACCLOAL
SPRCHRGN
CBLIFEAL
SPRCHRGD
NOOPRALM
CBCNTRST
PRESALM
IACCRST
PRESLO
SPCHTRST
CBOPEN
TRVTRST
CBINVPOS
52a
ANSI10000281-1-en.vsd
ANSI10000281 V1 EN
Figure 230:
SSCBR function block
Section 12
Monitoring
^
2 t values. Alarms are generated
525