Two Step Undervoltage Protection Uv2Ptuv (27) - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
Section 7
7.1
7.1.1
7.1.2
7.1.3
Technical manual
Voltage protection

Two step undervoltage protection UV2PTUV (27)

Identification
Function description
Two step undervoltage protection
Functionality
Undervoltages can occur in the power system during faults or abnormal conditions. Two
step undervoltage protection (UV2PTUV, 27) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed back-
up to primary protection.
UV2PTUV (27) has two voltage steps, where step 1 is settable as inverse or definite time
delayed. Step 2 is always definite time delayed.
UV2PTUV (27) has a high reset ratio to allow settings close to system service voltage.
Function block
UV2PTUV (27)
V3P*
TRIP
BLOCK
TRST1
BLK1
TRST2
BLK2
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
ANSI09000285-1-en.vsd
ANSI09000285 V1 EN
Figure 68:
UV2PTUV (27) function block
IEC 61850
IEC 60617
identification
identification
UV2PTUV
3U<
SYMBOL-R-2U-GREATER-THAN
V2 EN
Section 7
Voltage protection
ANSI/IEEE C37.2
device number
27
167