Section 10
Control
270
OPENPOS
CLOSEPOS
EXE_OP
EXE_OP
tStartMove timer
IEC05000099 V1 EN
Figure 123:
Open command with open position indication
Error handling
Depending on the error that occurs during the command sequence the error signal will be
set with a value. Table
196
specified in IEC 61850-8-1 standard. The list of values of the "cause" are in order of
priority. The values are available over the IEC 61850. An output L_CAUSE on the
function block indicates the latest value of the error during the command.
Table 196:
Vendor specific cause values for Apparatus control in priority order
Apparatus control
Description
function
–22
wrongCTLModel
–23
blockedForCommand
–24
blocked-for-open-command
–25
blocked-for-close-command
–30
longOperationTime
–31
switch-not-start-moving
–32
persistent-intermediate-state
–33
switch-returned-to-initial-position
–34
switch-in-bad-state
–35
not-expected-final-position
tOpenPulse
tOpenPulse
describes vendor specific cause values in addition to these
1MRK 511 287-UUS A
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000099.vsd
Technical manual