Technical Data - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 7
Voltage protection
7.3.8
7.4
7.4.1
7.4.2
186

Technical data

Table 128:
ROV2PTOV (59N) technical data
Function
Operate voltage, step 1
Operate voltage, step 2
Reset ratio
Inverse time
characteristics for low and
high step, see table
578
Definite time setting, step
1
Definite time setting, step
2
Minimum operate time for
step 1 inverse
characteristic
Operate time, pickup
function
Reset time, pickup
function
Critical impulse time
Impulse margin time
Loss of voltage check LOVPTUV (27)
Identification
Function description
Loss of voltage check
Functionality
Loss of voltage check LOVPTUV (27) is suitable for use in networks with an automatic
system restoration function. LOVPTUV (27) issues a three-pole trip command to the
circuit breaker, if all three phase voltages fall below the set value for a time longer than the
set time and the circuit breaker remains closed.
Range or value
VBase
(1-200)% of
(1–100)% of
VBase
> 98%
-
(0.00–6000.00) s
(0.000–60.000) s
(0.000-60.000) s
30 ms typically at 0 to 2 x V
set
40 ms typically at 2 to 0 x V
set
10 ms typically at 0 to 1.2 xV
set
15 ms typically
IEC 61850
identification
LOVPTUV
1MRK 511 287-UUS A
Accuracy
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
-
See table
578
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
-
-
-
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
27
Technical manual
n
n
n
n