Section 11
Logic
392
outputs, where one is inverted. The memory setting controls if the flip-flop after a power
interruption will return the state it had before or if it will be reset.
SRMEMORYQT propagates quality and time as well as value.
Table 305:
Truth table for SRMEMORYQT function block
SET
RESET
OUT
0
0
Last
value
0
1
0
1
0
1
1
1
1
If Memory parameter is Enabled, the output result is stored in semi-retained memory.
Function block
SRMEMORYQT
SET
OUT
RESET
NOUT
IEC09000301-1-en.vsd
IEC09000301 V1 EN
Figure 185:
SRMEMORYQT function block
Signals
Table 306:
SRMEMORYQT Input signals
Name
Type
SET
BOOLEAN
RESET
BOOLEAN
Table 307:
SRMEMORYQT Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
NOUT
Inverted
last value
1
0
0
Default
Description
0
Input signal to set
0
Input signal to reset
Description
Output signal
Inverted output signal
1MRK 511 287-UUS A
Technical manual