Section 12
Monitoring
12.15.2
12.15.3
12.15.4
516

Function block

SPVNZBAT
V_BATT
AL_VLOW
BLOCK
AL_VHI
PU_VLOW
PU_VHI
ANSI12000026-1-en.vsd
ANSI12000026 V1 EN
Figure 226:
Function block
Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
SPVNZBAT activates the start and alarm outputs when the battery terminal voltage
exceeds the set upper limit or drops below the set lower limit. A time delay for the
overvoltage and undervoltage alarms can be set according to definite time characteristics.
SPVNZBAT operates after a settable operate time and resets when the battery
undervoltage or overvoltage condition disappears after settable reset time.
Signals
Table 413:
SPVNZBAT Input signals
Name
Type
V_BATT
REAL
BLOCK
BOOLEAN
Table 414:
SPVNZBAT Output signals
Name
Type
AL_VLOW
BOOLEAN
AL_VHI
BOOLEAN
PU_VLOW
BOOLEAN
PU_VHI
BOOLEAN
Default
Description
0.00
Battery terminal voltage that has to be supervised
0
Blocks all the output signals of the function
Description
Alarm when voltage has been below low limit for a set
time
Alarm when voltage has exceeded high limit for a set
time
Pick up signal when battery voltage drops below lower
limit
Pick up signal when battery voltage exceeds upper limit
1MRK 511 287-UUS A
Technical manual