1MRK 511 287-UUS A
Technical manual
External analog
signals
Internal analog signals
IEC05000653 V2 EN
Figure 219:
Analog input function blocks
The external input signals will be acquired, filtered and skewed and (after configuration)
available as an input signal on the AxRADR function block via the SMAI function block.
The information is saved at the Disturbance report base sampling rate (1000 or 1200 Hz).
Internally calculated signals are updated according to the cycle time of the specific
function. If a function is running at lower speed than the base sampling rate, Disturbance
recorder will use the latest updated sample until a new updated sample is available.
Application configuration tool (ACT) is used for analog configuration of the Disturbance
report.
The preprocessor function block (SMAI) calculates the residual quantities in cases where
only the three phases are connected (AI4-input not used). SMAI makes the information
available as a group signal output, phase outputs and calculated residual output (AIN-
output). In situations where AI4-input is used as an input signal the corresponding
information is available on the non-calculated output (AI4) on the SMAI function block.
Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = Enabled means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and triggers
even if operation is set to Disabled. Both undervoltage and overvoltage can be used as
trigger conditions. The same applies for the current signals.
SMAI
GRPNAME
AI3P
AI1NAME
AI1
AI2NAME
AI2
AI3NAME
AI3
AI4NAME
AI4
AIN
Section 12
Monitoring
A1RADR
A2RADR
GRPINPUT1
A3RADR
GRPINPUT2
GRPINPUT3
GRPINPUT4
GRPINPUT5
GRPINPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
en05000653-2.vsd
485