Inputs And Outputs; Time Synchronization - ABB i-bus KNX ABA/S 1.2.1 Product Manual

Logic controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Group objects
8.2

Inputs and outputs

No.
1...500
This group object is defined via the logic editor.
Unique names can be entered in the logic editor Properties window.
Table 8: Inputs and outputs
8.3

Time synchronization

No.
501
For a description, see
502
This group object queries the date/time from a time master after device start-up.
30 seconds after start-up this group object will send a 1.
503
This group object receives the date.
504
This group object receives the time.
Only time information is evaluated. Day of the week information is not taken into account.
505
This group object receives the combined date and time.
Only date and time is evaluated. Other information provided by this datapoint (e.g. year or weekday) is not taken into account.
Table 9: Time synchronization
104 2CDC509086D0201 | ABA/S 1.2.1
Object Function
Applied from the logic editor
Object Function
In operation
Send Group Object "In Operation" (1-bit)
Request object
Date
Time
Date/Time
Name
Blank
Name
General
Device Clock
Device Clock
Device Clock
Device Clock
Data type
Flags
According to the
C, R, W, T
definition in the
logic editor
Data type
Flags
1 bit
C, T
DTP 1.001
1 bit
C, T
DPT 1.017
3 byte
C, R, W
DPT 11.001
3 byte
C, R, W
DPT 10.001
8 byte
C, R, W
DPT 19.001

Hide quick links: