Energy Saving Operation And Energy Saving Monitor; Energy Saving Monitor (Pr. 891 To Pr. 899) - Mitsubishi Electric FR-B-750 to 75K Instruction Manual

Fr-b-750 to 75k (200v class), fr-b-750 to 110k (400v class)
Table of Contents

Advertisement

Energy saving operation and energy saving monitor

4.15 Energy saving operation and energy saving monitor
Purpose
How much energy can be saved

4.15.1 Energy saving monitor (Pr. 891 to Pr. 899)

From the power consumption estimated value during commercial power supply operation, the energy saving
effect by use of the inverter can be monitored/output.
Parameter
Name
Number
DU/PU main display
52
data selection
FM terminal function
54
selection
AM terminal function
158
selection
Cumulative power
891
monitor digit shifted
times
892
Load factor
Energy saving monitor
893
reference (motor
capacity)
Control selection
894
during commercial
power-supply operation
Power saving rate
895
reference value
896
Power unit cost
Power saving monitor
897
average time
Power saving
898
cumulative monitor
clear
Operation time rate
899
(estimated value)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
* The setting range differs according to the inverter capacity. (55K or less/75K or more)
160
Parameter that must be Set
Energy saving monitor
Setting Range
Initial
Value
FR-B
0
0, 5, 6, 8 to 14, 17
(output
to 20, 22 to 25,
frequency)
50 to 57, 100
1
1 to 3, 5, 6, 8 to
(output
14, 17, 18, 21,
frequency)
24, 50, 52, 53
0 to 4
9999
9999
100%
30 to 150%
Inverter
rated
0.1 to 55kW/0 to 3600kW *
capacity
0
9999
9999
0 to 500
9999
9999
9999
1 to 1000h
9999
9999
9999
0 to 100%
9999
9999
Pr. 52, Pr. 54, Pr. 158,
Pr. 891 to Pr. 899
FR-B3
0, 5 to 14, 17
to 20, 22 to 25,
50:Power saving monitor
34, 50 to 57,
51:Cumulative saving power monitor
100
1 to 3, 5 to 14,
17, 18, 21, 24,
50:Power saving monitor
50, 52, 53
Set the number of times to shift the
cumulative power monitor digit
Clamps the monitoring value at maximum.
No shift
Clears the monitor value when it exceeds
the maximum value.
Set the load factor for commercial power-
supply operation. Multiplied by the power
consumption rate (page 163) during
commercial power supply operation.
Set the motor capacity (pump capacity).
Set when calculating power saving rate,
power saving rate average value,
commercial operation power.
0
Discharge damper control (fan)
1
Inlet damper control (fan)
2
Valve control (pump)
Commercial power-supply drive (fixed
3
value)
Consider the value during commercial
0
power-supply operation as 100%
1
Consider the Pr. 893 setting as 100%.
No function
Set the power unit cost. Displays the
power saving amount charge on the
energy saving monitor.
No function
0
Average for 30 minutes
Average for the set time
No function
0
Cumulative monitor value clear
1
Cumulative monitor value hold
Totalization continued
10
(communication data upper limit 9999)
Totalization continued
(communication data upper limit 65535)
Use for calculation of annual power saving
amount. Set the annual operation ratio
(consider 365 days × 24hr as 100%).
No function
Refer to
Page
160
Description