Command
To send an operation command to the Temperature Controller, set the items in
the command text as follows:
Command Text
Command
Related
MRC
SRC
code
information
"30"
"05"
2
2
2
2 bytes
Item
MRC/SRC
Specify the FINS-mini operation command (operation com-
mand service).
Command code
Place a command code in this field.
Related information
Place information related to the operation command in this
field.
E5ZN Command Codes
Command
Command code
code
"00"
Communications
writing
"01"
RUN/STOP
"02"
Multi-SP
"03"
AT execute/cancel
"04"
Write mode
"05"
RAM data save
"06"
Software reset
"07"
Move to setting area 1 "00" or "10"
"08"
Move to protect level
"09"
Auto/manual
Description
Related information
"00" or "10": OFF (disable)
"01" or "11": ON (enable)
"00": Run ch1
"01": Stop ch1
"10": Run ch2
"11": Stop ch2
"F0": Run ch1, ch2 (See note 1.)
"F1": Stop ch1, ch2 (See note 1.)
"00": Select SP0 for ch1
"01": Select SP1 for ch1
"10": Select SP0 for ch2
"11": Select SP1 for ch2
"F0": Select SP0 for ch1, ch2 (See note 1.)
"F1": Select SP1 for ch1, ch2 (See note 1.)
"00": Stop ch1 AT
"01": Execute ch1 AT
"10": Stop ch2 AT
"11": Execute ch2 AT
"F0": Stop ch1, ch2 AT (See note 1.)
"F1": Execute ch1, ch2 AT (See note 1.)
"00" or "10": Backup
"01" or "11": RAM
"00" or "10"
"00" or "10"
"00" or "10"
"00": Auto for ch1
"01": Manual for ch1
"10": Auto for ch2
"11": Manual for ch2
"F0": Auto for ch1, ch2 (See note 1.)
"F1": Manual for ch1, ch2 (See note 1.)