Analog Output Units

Calculation Example
5-5
Analog Output Units
5-5-1

GRT1-DA2C/GRT1-DA2V Analog Output Units

General Specifications
Item
Unit power supply voltage
I/O power supply voltage
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Ambient temperature
Ambient humidity
Operating environment
Storage temperature
Mounting
Performance Specifications
Item
Output points
Output type
Output range setting method
External output allowable load resistance
Resolution
Overall accuracy
25°C
–10 to 55°C
Conversion time
The following table shows the additional time required for each function
(unit: ms).
Math operation
Additional time for each point
Moving average
0.045
Scaling
0.055
Peak/bottom hold
0.025
Top/valley hold
0.070
Comparator
0.065
Rate of change
0.030
Cumulative counter
0.035
When using two points, and applying scaling to the first input, and the cumula-
tive counter to the second input, the maximum AD conversion cycle time can
be obtained by using the following formula.
Formula: 2.42 + 0.055 + 0.035 = 2.51 ms
24 VDC (24 VDC −15% to +10%)
I/O power supply not required.
Conforms to IEC 61000-4-4. 2.0 kV (power lines)
10 to 60 Hz, 0.7-mm double amplitude; 60 to 150 Hz, 50 m/s
2
150 m/s
500 VAC for 1 min. with 1-mA sensing current (between communications and
analog circuits)
–10 to 55°C (with no icing or condensation)
25% to 85% (with no condensation)
No corrosive gases
–25 to 65°C (with no icing or condensation)
35-mm DIN Track mounting
GRT1-DA2V Voltage output
2 points (outputs 0 and 1)
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
• DIP switch: Outputs 0 and 1 set separately.
• Setting Tool: Outputs 0 and 1 set separately.
5 kΩ min.
1/6,000 (full scale)
±0.4% FS
±0.8% FS
2 ms/2 points
Specifications
Specifications
GRT1-DA2C Current output
0 to 20 mA
4 to 20 mA
350 Ω max.
±0.4% FS (See note.)
±0.8% FS (See note.)
Section 5-5
2
137