Grounding Multiple Pieces Of Equipment In A Rack/Cabinet - Nortel Meridian 1 Planning And Installation Manual

Table of Contents

Advertisement

Page 122 of 590

Grounding multiple pieces of equipment in a rack/cabinet

553-3021-209
Standard 1.00
Chapter 11 – Installing the system ground
5
Place a DO NOT DISCONNECT tag on the ground wire at the
service panel.
6
Test the ground.
—————————— End of Procedure ——————————
Procedure 8
UK grounding procedure for the Option 11C Mini chassis
1
Connect a protective and functional ground wire from the
grounding strip on the Krone Test Jack Frame to the ground at
the building entry point.
Use a green/yellow wire no thinner than 10 mm
2
In each chassis, connect a ground wire from the ground lug in the
chassis to the ground connection at the Test Jack Frame.
See Figure 37 on page 121.
Use a green/yellow wire no thinner than 10 mm
DISCONNECT tag on the grounding wire.
3
Measure the resistance of the ground between the Krone Test
Jack Frame and the Main Chassis frame ground.
The resistance must not be more than 0.25
—————————— End of Procedure ——————————
For multiple pieces of equipment installed in a rack/cabinet, make a separate
ground connection from each piece of equipment to the NTBK80 grounding
block. See Figure 38.
If a piece of Data Communications Equipment installed in a rack/cabinet does
not have a ground lug, ground the rack to the NTBK80 grounding block. See
Figure 38.
When you ground the rack to the grounding block, the equipment is grounded
using the Single Point Grounding method, as shown in Figure 5 on page 34.