Chapter 3 — System and site requirements
•
All conductors must be terminated in a permanent way. Make sure all
terminations are easily visible and available for maintenance purposes.
•
Tag ground connections clearly with a message such as "CRITICAL
CONNECTION: DO NOT REMOVE OR DISCONNECT".
Table 6
Region-specific grounding wire requirements
Region
Germany
Other regions in Europe
UK
When the Option 11C Mini is installed, the impedance of the link
between the ground post of the Main Chassis and the single point
ground to which it is connected must be less than 0.25 Ohms.
Reliable Option 11C Mini operation depends on high-precision
internal circuitry, which can be damaged by transients in its supply
conductors and ground system. Damage to sensitive devices, due to
transients, is not always immediately apparent: degradation can occur
over longer periods of time.
Grounding wire requirements
#8 AWG (10 mm
not smaller than #6 AWG (16 mm
point
two green/yellow wires no thinner than two
2
10 mm
CAUTION
CAUTION
Option 11C Mini
Planning and Installation Guide
Page 31 of 590
2
) green/yellow wire
2
) at any