Chassis powered by the same service panel
Chassis powered by different service panels
553-3021-209
Standard 1.00
Chapter 11 – Installing the system ground
For each system chassis in collocated multi-chassis configurations, connect a
#6 AWG (#40 Metric Wire Gauge) ground wire from the chassis to an
NTBK80 grounding block. The grounding block is in turn connected to a
ground source (the ground bus in the AC service panel). See Table 17 for
region-specific grounding requirements.
For each system chassis in collocated multi-chassis configurations, connect a
#6 AWG (#40 Metric Wire Gauge) ground wire from the chassis to an
NTBK80 grounding block. If any chassis cannot be powered from the same
service panel, ground it separately from the other chassis back to the service
panel that supplies it. See Table 17 for region-specific grounding
requirements.
Table 17
Region-specific grounding wire requirements
Region
Germany
Other regions in Europe
UK
July 1999
Grounding wire requirements
2
#8 AWG (10 mm
) green/yellow wire
not smaller than #6 AWG (16 mm
point
two green/yellow wires no thinner than
2
two 10 mm
2
) at any