Nortel Meridian 1 Option 11C Planning And Installation Manual page 254

Hide thumbs Also See for Meridian 1 Option 11C:
Table of Contents

Advertisement

Page 254 of 408
Connecting the telephones
553-3021-210
Standard 7.00
Procedure 43
Connecting an off-premise telephone
1
Mount the NTAK92AA Off-Premise protection module on the wall
using four #10 1/2 in (minimum) screws.
2
Connect a #6 AWG (#40 Metric Wire Gauge) from the ground lug
at the bottom of the NTAK92AA Off-Premise protection module to
an earth ground. Refer to Figure 96 on page 256.
If connecting to a message waiting line card, unseat the card from its
assigned slot before proceeding with the next step.
3
Connect two NTAK9204 cables (one from connector J1 and one
from connector J2) from the protection module to the
cross-connect terminal.
Terminate the cables as shown in Figure 94 on page 250.
4
Cross-connect the J1 cable to the Tip and Ring connections
coming from the line card.
Default DN assignments are given in the following Tables:
• Table 42, "Main Cabinet Default DN assignments," on
page 263
• Table 43, "Expansion Cabinet 1 Default DN assignments," on
page 264
• Table 44, "Expansion Cabinet 2 Default DN assignments," on
page 265
• Table 45, "Expansion Cabinet 3 Default DN assignments," on
page 267
• Table 46, "Expansion Cabinet 4 Default DN assignments," on
page 268
5
Cross-connect the J2 cable to the off-premise telephone.
6
Install the regulatory label provided with the Off-Premise
protection module on the inside right-hand wall of the cabinet
near the velcro wriststrap fastener.
January 2002
WARNING