Nortel Meridian 1 Option 11C Planning And Installation Manual page 186

Hide thumbs Also See for Meridian 1 Option 11C:
Table of Contents

Advertisement

Page 186 of 408
Installing power fail transfer units
PFTU control lead signals
Table 18
PFTU control lead signals
NTAK1104 Aux. Cable
Lead
BRTN
BRTN
-48V AUX
PFTS
553-3021-210
Standard 7.00
To connect PFTUs from other manufacturers, use the information provided
in the following table:
Lead State when PFTU in
Non-Transferred State
GROUND
GROUND
-48V DC (250 mA max.)
Note 1: Refer to Figure 77 on page 183 for an illustration of where the
Auxiliary cable connects to the Option 11C system.
Note 2: If power is removed from the QUA6, a transfer of the PFTU
may also be invoked.
January 2002
OPEN
Lead State when PFTU in
Transferred State
GROUND
GROUND
-48V DC (250 mA max.)
GROUND