Nortel Meridian 1 Option 11C Planning And Installation Manual page 159

Hide thumbs Also See for Meridian 1 Option 11C:
Table of Contents

Advertisement

Incorrectly connected fiber optic cables may cause the following
problems:
– a series of repetitive fault indicating messages
– a complete failure of the expansion cabinet.
If fault indicating messages appear, check the fiber optic cable
connections.
Since messages are stored in a buffer, they may continue to be
displayed until the buffer is empty. After checking the cable
connections, wait a couple of minutes for the messages to stop.
Procedure 16
Installing the A0632902 10m plastic fiber optic cable:
1
Put on the anti-static wrist strap.
2
Place the SSC card on a clean flat surface.
3
Remove the protective plugs from the connectors on the Fiber
Daughterboard.
4
Connect the fiber optic cable to the Fiber Daughterboard making
sure that the 'V' shaped groove on the cable connector is facing
outward and that the connector is fully seated. See Figure 66 on
page 160.
The mark (if equipped) on the sides of the cable connector should
not be visible when properly connected. Refer to Figure 68 on page
162.
5
Route the fiber cable through the SSC cable router on the SSC
card.
6
Insert the SSC card into slot "0" of the main Option 11C cabinet.
Lock card into face plate latches.
Installing System Controller Cards Page 159 of 408
CAUTION
Option 11C
Planning and Installation Guide