Installing and connecting reserve power supplies Page 205 of 408
• The battery unit must be installed beside or below the Option
11C cabinet; not above.
• If installed below, the minimum clearance from the top of the
NTAK76 to the bottom of the wall mounted Option 11C cabinet
is 2 ft (610 mm).
• The battery unit should be installed in an open, well-ventilated
area.
• The area must meet the following temperature limits:
Maximum allowed range: 0 °to 45° C (32 to 110°F)
Recommended range: 20 ° to 35° C (68 to 95 °F)
2
Remove the cover
The cover is secured by one captive screw on the front of the box.
(Refer to Figure 84 on page 206).
3
Mount the battery unit to the wall using the four #8 3/4 inch wood
screws provided with the unit.
Install the center screw at the top of the battery unit. Level the unit and
install the remaining screws.