Three-Phase 200 V Class Drive Models 2O0104 To 2O0248 - YASKAWA U1000 iQpump MATRIX Drive User Manual

Low harmonic regenerative pump controller
Hide thumbs Also See for U1000 iQpump MATRIX Drive:
Table of Contents

Advertisement

u

Three-Phase 200 V Class Drive Models 2o0104 to 2o0248

Item
Drive Model
Maximum Applicable
Motor Capacity kW (HP)
Rated Input Current (A)
Rated Input Capacity (kVA)
Rated Output Current (A)
Input/Output
Overload Tolerance
Rating
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Rated Frequency
Allowable Voltage Fluctuation
Power Supply
Allowable Frequency Fluctuation
Allowable Phase Power Supply Voltage
Harmonic Current Distortion
Input Power Factor
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 240 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
Table A.2 Power Ratings (Three-Phase 200 V Class) Continued
<1>
<2>
<3>
<4> <5>
Rated Voltage
Unbalance
<6>
2o0104
2o0130
30 (40)
37 (50)
95
118
43
54
104
130
Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
4 kHz (User adjustable up to 8 kHz. Derating may be required.)
Proportional to input voltage
400 Hz (User-adjustable)
Three-phase 200 to 240 Vac 50/60 Hz
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
5% or less (IEEE519 compliant)
0.98 or more (During rated operation)
A.1 Power Ratings
Specification
2o0154
2o0192
45 (60)
55 (75)
140
175
64
80
154
192
<6>
-15 to 10%
2% or less
2o0248
75 (100)
226
103
248
4 kHz
A
265