<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be set up to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.

◆ Three-Phase 600 V Class Drives

Item
CIMR-LU5A
0003 0004 0006 0010 0013 0017 0022 0027 0032 0041 0052 0062 0077 0099 0130 0172 0200
Maximum Applicable
Motor Capacity
2
(HP)
<1>
Input Current
3.6
(A)
<2>
Rated Voltage
Rated
Frequency
Allowable
Input
Voltage
Fluctuation
Allowable
Frequency
Fluctuation
Input Power
4.1
(kVA)
Rated Output
3.5
Capacity
<5>
(kVA)
<3>
Rated Output
3.5
Current (A)
<5>
Overload
Tolerance
Outpu
Carrier
User adjustable between
t
Frequency
Maximum
Output
Voltage (V)
Maximum
Output Speed
(Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be set up to 3 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be set up to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Table 57 Power Ratings (Three-Phase 600 V Class)
3
5
7.5
10
15
5.1
8.3
12
16
23
5.8
9.5
14
18
26
4.1
6.3
9.8
12
17
<5>
<5>
<5>
<5>
<5>
4.1
6.3
9.8
12.5
17
<5>
<5>
<5>
<5>
<5>
2 and 15 kHz
Three-phase 500 to 600 Vac (proportional to input voltage)
Specification
20
25
25-30
40
50-60 50-60
31
38
33
44
Three-phase 500 to 600 Vac 50/60 Hz
-10 (-15) to 10%
±5%
35
43
38
50
22
27
32
41
<5>
<5>
<5>
<5>
22
27
32
41
<5>
<5>
<5>
<5>
150% of rated output current for 60 s
User adjustable between
2 and 10 kHz
200 Hz (user-adjustable)
A Specifications
75
100
125
54
66
80
108
129
62
75
91
123
147
52
62
77
99
129
<5>
<5>
<6>
<4>
<4>
52
62
77
99
130
<5>
<5>
<6>
<4>
<4>
User
adjustab
le
User adjustable between
between
2 and 3 kHz
2 and 8
kHz
150
250
158
228
181
261
171
199
<4>
<4>
172
200
<4>
<4>