5. Enter mountstate –getobject –enclosure and press Enter to list the mount
6. Enter list enclosure and press Enter to display the firmware version of the
7. Enter mountstate -setobject –dismount -enclosure 1 –okdegraded and press
8. Enter alert – get and press Enter to query the active alert list. Ensure alert
170
IBM SAS RAID Controller Module: Installation and User's Guide IBM BladeCenter S SAS RAID Controller Module
FOR=foreign
CBL/SCL=current/stale auto-copy-back local spare
GLS/SGS=current/stale global spare
CBG/SCG=current/stale auto-copy-back global spare
State: OK=healthy
U=unreliable (M/P/U can be combined)
INI=initialized UNS=unsupported (non-IBM) drive
IMD=incompatible metadata with this software version; either assimilate drive or
update controller firmware.
UNF=firmware version unsupported for drive
state of the DSM that is being replaced. Ensure that each DSM is online.
<CLI> mountstate -getobject -enclosure
Current Machine Local Time: 09/15/2009 02:08:29 PM
_______________________________________________________
| Enclosure# | State
|_____________|_______________________|_________________|
| 0
| Online
| 1
| Online
| 2
| Online
|_____________|_______________________|_________________|
DSMs. Record the firmware version of each DSM.
<CLI> list enclosure
Current Machine Local Time: 09/15/2009 02:09:06 PM
_____________________________________________________________________________
| Encl#
| Enclosure
|_____________|________________|_________________|________________|___________|
| 0
| Encl0
| 1
| Encl1
| 2
| Encl2
|_____________|________________|_________________|________________|___________|
Enter to dismount the DSM that you will replace. The RAID controller
prepares the DSM for service by dismounting the DSM and the disk drives
inside the DSM.
<CLI> mountstate -setobject -dismount -enclosure 1 -okdegraded
Current Machine Local Time: 09/15/2009 02:16:00 PM
Set Enclosure MountState successful
2000 was generated for the DSM that was dismounted, and ensure alert 2300
was generated for each disk drive in the DSM that was dismounted.
<CLI> alert -get
Current Machine Local Time: 09/15/2009 02:16:27 PM
Existing Alerts :
_________________________________________________________________________________________
|AlertCode| Id | Time
|=========================================================================================|
| 2000
| 21 | 20090915141600 | 0
|-----------------------------------------------------------------------------------------|
| Msg: Dismounted drive enclosure 1 ready to remove
|=========================================================================================|
| 2300
| 38 | 20090915141523 | 1
|-----------------------------------------------------------------------------------------|
| Msg: Drive 01:01 ready for removal
|=========================================================================================|
| 2300
| 40 | 20090915141523 | 1
|-----------------------------------------------------------------------------------------|
| Msg: Drive 01:02 ready for removal
|=========================================================================================|
| 2300
| 39 | 20090915141523 | 1
LCS/SLS=current/stale local spare
M=missing
P=PFA predicted failure
| Type
| Controller
| DSM
| DSM
| Type
| Version
| Controller
| 0107
| DSM
| 1.08
| DSM
| 1.08
| SlotID | Severity |WWN
| Info
| Info
| Info
| Info
PM=path missing
|
|
|
|
| Status
| Good
| Good
| Good
| Ackable | MaskState|
|5005076b0741417f| 0
|5005076b0741417f| 0
|5005076b0741417f| 0
|5005076b0741417f| 0
|
|
|
|
| Unmasked |
|
| Unmasked |
|
| Unmasked |
|