Did fan module (power supply) replacement solve the problem?
NO
Contact the next level of support. Exit MAP.
7
A power supply failed POSTs (as indicated by FRU code 06) and must be
removed and replaced. Refer to
Did power supply replacement solve the problem?
NO
Contact the next level of support. Exit MAP.
Edge Switch 2/24 Service Manual
Perform the data collection procedure as part of FRU removal and
replacement.
If multiple power supply failures occurred, connect the switch to facility AC
power after both power supplies are replaced.
Caution:
Do not remove a power supply unless a replacement FRU is
immediately available. To avoid product overheating, a removed power supply
must be replaced within five minutes.
YES
The switch appears operational. Exit MAP.
This procedure is concurrent and can be performed while switch power is on.
Perform the data collection procedure as part of FRU removal and
replacement.
If multiple power supply failures occurred, connect the switch to facility AC
power after both power supplies are replaced.
Caution:
Do not remove a power supply unless a replacement FRU is
immediately available. To avoid product overheating, a removed power supply
must be replaced within five minutes.
YES
The switch appears operational. Exit MAP.
"RRP: Redundant Power
Diagnostics
Supply" on page 198.