Specifications

5 Specifications

5.1 Technical Design Considerations

WARNING
FUNCTIONAL-SAFETY COMPLIANT USE
®
The VLT
Plus Panel is a product in accordance with the
Low Voltage Directive 2006/95/EG, but does not provide
safety-related control functionality in accordance with
Machine Safety Directive 2006/42/EG. CE declaration is
therefore related to EMC (2004/108/EG) and LV Directive.
Failure to take the necessary safety-related control
measures can result in death or serious injury.
The panel operator has to ensure the proper
use of the product, even when Safe Torque Off
(STO) functionality is used, for example for
ATEX-conform motor thermal protection. In this
case, the safety function is part of the approved
motor thermal protection, using the function as
appropriate energy cut-off.
Any other use of the safety functions is in sole
responsibility of the end user, including certifi-
cation, documentation, and so on.
Customized variants can differ and are not
subject to the panel configurator product
description.
NOTICE
The notification of maximum possible cross-section and
number of wires is shown in drawings for each main
component, where mains and motor cables can be
directly connected. The drawings are provided with the
panel.
Power
I
1)
Fuse
CW
[kW]
90 kW
3NA7 140
2.2 kA
110 kW
3NA7 144
2.9 kA
132 kW
3NA7 252
4 kA
160 kW
3NA7 260
5.1 kA
200 kW
3NA3 365
7.7 kA
250 kW
3NA3 365
7.7 kA
315 kW
3NA3 372
10.5 kA
Table 5.2 Short Circuit Withstand Capability According to DIN EN 61439
1) Siemens example; fuses with same characteristics from other suppliers can be used.
MG13B102
Installation Guide
(200 ms)
I
C
5.6 kA
7.4 kA
10.2 kA
12.9 kA
19.5 kA
19.5 kA
26.8 kA
Danfoss A/S © 09/2015 All rights reserved.
Electrical specifications
Mains supply 400 V, 500 V, or 690 V, PEN, 3-phase, 50 Hz, IT or
TN, as selected.
Maximum
I
= 35 kA on infeed terminals of the panel, see
CW
short circuit
Table 5.2.
capabilities
Assembly
In accordance with the relevant frequency
rated current
converter current rating.
NOTICE
I
nA
®
For VLT
(normal overload) values are used for the
design. Due to the 80% design rule of EN
61439-2, design is adjusted for the HO
(high overload) use. Details are provided
per power rating in the relevant
documents.
RDF
RDF is specified to 1 for all power circuitry as
only 1 frequency converter is foreseen per panel/
infeed.
Cables/wires
Cables/wires used according to DIN standards,
cross-section in mm
can be used. Always consider local standards
must always be taken into considerations.
Energy
Energy cabling is done directly to the relevant
cabling
terminals of switchgear, frequency converter, or
filter.
Cable entry
Bottom cable entry.
Wiring color
According to DIN EN 60204-1.
code
Table 5.1 Electrical Specifications
Let through energy
I
for I
@35
CC
CW
(200 ms)
kA
15 kA
945 kA
2
s
19.3 kA
1673 kA
2
s
24.1 kA
2
3238 kA
s
29.5 kA
5508 kA
2
s
39.3 kA
11409 kA
2
s
39.3 kA
2
11409 kA
s
48.7 kA
21848 kA
2
s
AutomationDrive FC 302, NO
2
. Any specified power cable
2
I
t@35 kA
PE [mm
30x5
400 kA
2
s
30x5
780 kA
2
s
30x10
2
1275 kA
s
30x10
2150 kA
2
s
30x10
2700 kA
2
s
30x10
2
2700 kA
s
30x10
5400 kA
2
s
5
5
2
]
29