Configuring The Status Input; Configuring The Current Output - Endress+Hauser Proline Promass A 300 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass A 300 PROFINET
Parameter
Terminal number
Assign status input
Active level
Response time status input
Endress+Hauser
10.5.7

Configuring the status input

The Status input submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.
Navigation
"Setup" menu → Status input
Status input 1 to n
Assign status input
Terminal number
Active level
Terminal number
Response time status input
Terminal number
Parameter overview with brief description
Description
Shows the terminal numbers used by the
status input module.
Select function for the status input.
Define input signal level at which the
assigned function is triggered.
Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
10.5.8

Configuring the current output

The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
Current output 1 to n
Terminal number
User interface / Selection / 
User entry
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
• Zero point adjustment
• High
• Low
5 to 200 ms
Commissioning
→  99
→  99
→  99
→  99
→  99
→  99
Factory setting
Off
High
50 ms
→  100
99

Advertisement

Table of Contents
loading

Table of Contents