ABB AC500 PLC Hardware Manual page 281

Table of Contents

Advertisement

State LEDs
LED
Technical Data
The System Data of AC500-eCo apply
on page 1192
Only additional details are therefore documented below.
Parameter
Process supply voltage UP
Current consumption from 24 VDC power supply
at the L+/UP and M/ZP terminals of the CPU/bus
module
Galvanic isolation
Isolated groups
Surge-voltage (max.)
Max. power dissipation within the module
Weight
Mounting position
Cooling
No effects of
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
multiple over-
protected individually by an external fuse.
loads
2019/04/17
Inputs I0...I7
Outputs
O0...O7
Connections
Rated value
Current consumption via UP terminal
Max. ripple
Inrush current
Protection against reversed voltage
Rated protection fuse for UP
3ADR010121, 13, en_US
State
Color
Digital input
Yellow
Digital output Yellow
Ä Chapter 2.5.1 "System Data AC500-eCo"
Value
Terminal 19 for UP (+24 VDC) and ter-
minal 20 for ZP (0 VDC)
24 VDC
5 mA + max. 0.5 A per output
5 %
0.000002 A²s
Yes
Recommended; the outputs must be pro-
tected by an 3 A fast fuse
Ca. 10 mA
Yes, between the input group and the
output group and the rest of the module
2 groups (1 group for 8 input channels, 1
group for 8 output channels)
35 VDC for 0.5 s
2.3 W
ca. 120 g
Horizontal or vertical
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switch-gear cabinet.
Device Specifications
I/O Modules > Digital I/O Modules
LED = OFF
LED = ON
Input is OFF Input is ON
Output is
Output is ON
OFF
281