With the server top cover removed, install the replacement fan module into the server.
2.
The fan modules are keyed to ensure that they are installed in the correct orientation.
Press down on the fan module to fully seat the fan module.
3.
Verify that the fan module status indicator (LED) for the replacement fan module is not
4.
illuminated.
Install the server top cover.
5.
See
Verify that the Top Fan Fault LED on the front of the server and the Fault-Service
6.
Required LEDs on the front and back of the server are not illuminated.
See
interpreting system status indicators.
Consider your next step:
7.

Remove the Fan Tray

Perform this procedure only when servicing Disk backplane, SAS cables, and Motherboard
assembly replaceable components.
Remove all fan modules from the fan tray.
1.
See
Remove the air baffle.
2.
See
Using a Torx T25 screwdriver, loosen the five spring-mounted screws that secure the fan
3.
tray to the server chassis.
Install the Server Top
Cover.
System-Level Status Indicators
If you installed the fan module as part of another procedure, return to that procedure.
Otherwise, return the server to operation. See
Remove a Fan
Module.
Remove the Air
Baffle.
for more information about identifying and
Returning the Server to
Chapter 6
Remove the Fan Tray
Operation.