Install The Server Into The Slide-Rail Assemblies - Oracle Exadata X10M Service Manual

Table of Contents

Advertisement

Align the front of the slide-rail assembly against the outside of the front rack rail,
3.
and push until the assembly locks into place with an audible click.
Repeat Step 1 through Step 3 to attach the slide-rail assembly to the other side of
4.
the rack.

Install the Server Into the Slide-Rail Assemblies

Use this procedure to install the server chassis with mounting brackets into the slide-
rail assemblies that are mounted to the rack.
Caution:
Personal Injury or Equipment Damage: This procedure requires a
minimum of two people because of the weight of the server. Attempting this
procedure alone could result in equipment damage or personal injury.
Always load equipment into a rack from the bottom up so that the rack does
not become top-heavy and tip over. Extend the rack anti-tilt bar to prevent
the rack from tipping during equipment installation.
Push the slide-rails as far as possible into the slide-rail assemblies in the rack.
1.
Position the server so that the back ends of the mounting brackets are aligned with
2.
the slide-rail assemblies that are mounted in the rack.
Appendix C
Rackmounting the Server
C-14