5.4.6 AC500 V3 firmware installation and update

The PLC firmware can be updated via Automation Builder.
A very new CPU has no pre-installed firmware. To guarantee the authenticity of delivered
AC500 firmware, V3 CPUs are delivered with a boot loader only. You need to download a valid
firmware to the CPU. After download, the functionality of the CPU is given.
42
Double-click "PLC_AC500_V3" in the device tree.
Select "Communication Settings".
ð The selected IP address is shown.
If the IP address is not visible, enter the IP address manually.
To test the connection and/or to see the CPU information press [Enter] or click on the
black dot next to the PLC picture.
This is also necessary for commissioning AC500-eCo V3 CPUs.
An Automation Builder project with an AC500 V3 CPU is open.
CPU is in "stop" mode without firmware.
The power LED is ON.