Bulk Power Supply Failed Fieldbus Power Supply; Cable Breakage, Short Cir- Cuit Or Terminal Connection Failure; Check Bulk Power Supply Install Fieldbus Power Sup - Pepperl+Fuchs HD2-DM-A Manual

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Appendix
ID
146
149
150
152
153
154
155
156
Phenomenon
Signal level of one or more
devices is too high
Segment voltage is mea-
sured as zero. Segment is
unpowered
The segment is powered
and communication is
active, but no devices are
detected
Noise "MR/OOS" for the
segment
Jitter of one device
"MR/OOS", jitter of other
devices OK
Unbalance is "OOS/MR" to
fieldbus +
Unbalance is "OOS/MR" to
fieldbus -
Noise of one device is
"MR/OOS", value of other
devices is not "MR/OOS"
Cause(s)
Not enough terminators
Fieldbus power supply
failed
Bulk power supply failed
Fieldbus power supply
removed
Cable breakage, short cir-
cuit or terminal connection
failure
Diagnostic device is
wrongly or not connected
to the segment
Wrong fieldbus type
selected
Noise injection on the field-
bus
Shield wiring / grounding
fault
Device malfunction: jitter of
a device is too high
Not enough terminators
Fieldbus impedance fault
Short circuit/leakage cur-
rent between fieldbus pos.
pole and shield/ground
Water ingress
Short circuit/leakage cur-
rent between fieldbus neg.
pole and shield/ground
Water ingress
Device injects noise
Action(s)
Check if a terminator is
installed on both ends of
the trunk
Replace fieldbus power
supply module
Check bulk power supply
Install fieldbus power sup-
ply
Check cabling and termi-
nals
Check wiring connection to
the segment
Set fieldbus type to FOUN-
DATION Fieldbus or PRO-
FIBUS PA
Check fieldbus cable for
correct shielding and
grounding. Check for exter-
nal noise sources.
Check fieldbus cable for
correct shielding and
grounding.
Replace device
Check if a terminator is
installed on both ends of
the trunk
Check if the fieldbus topol-
ogy is valid. Check noise,
reduce high noise values.
Remove connection
between pos. pole and
shield/ground
Check housings of devices
and junction boxes for
water ingress
Remove connection
between neg. pole and
shield/ground
Check housings of devices
and junction boxes for
water ingress
Check noise with the field-
bus oscilloscope. The
device showing high noise
values is not necessarily
the one injecting the noise.
177