Advanced Diagnostics
FOUNDATION Fieldbus Integration
6.4.1
Configuration
It is recommended to use the commissioning wizard for configuration of the segment, since this
is the fastest and safest way of adjusting the maintenance limits. However, it is also possible to
configure a segment manually; all necessary settings are available as FF parameters. For sys-
tems that do not support all EDDL (DD5) features, a list of parameters of the ADM_TB is avail-
able. See chapter 8.2.1
System
Block tag: Block tag of the ADM_TB.
History period: Time difference between non-volatile storage of segment measurement
entry. These entries can only be read using the history export function. See chapter 5.11
Identify diagnostic module: Causes LEDs of diagnostic module to flash.
ADM firmware update: Updates the advanced diagnostic module (ADM) to the firmware
built into the HD2–GT–2AD.FF.IO device. Only 1 ADM can be updated at a time. Check
the expert diagnostic messages in the diagnostic segment user interfaces for the update
status.
Segment
Segment tag: Tag of the segment. Should be set to the same tag as the physical segment
for reference.
Segment mode: Select the segment mode. For more information on the segment mode,
see chapter 2.
Power supply real-time monitoring: Enables or disables real-time monitoring of power
supplies. When checked, an alarm is generated when a power supply module is not
inserted or not working correctly. This setting is effective in commissioned mode only.
Trunk surge protector alarm: When enabled, trunk surge protector alarms are monitored.
This setting is effective in commissioned mode only.
Segment X commissioning button-method: Starts commissioning wizard. See chapter
6.5.1
Segment X commissioning (simple-mode-) method: Starts a simple commissioning
method. This approach is useful for hosts that do not support the necessary EDDL fea-
tures for the full-blown commissioning wizard.
Segment X tag import (simple-mode-) method: Starts a simple tag import method. This
approach is useful for hosts that do not support the necessary EDDL features for the full-
blown commissioning wizard.
Topology
Topology information is used in non-commissioned mode to refine diagnostics. The quality of
the expert system messages is improved if the topology of the segment is known.
Configuration grid
The configuration grid provides the possibility to change the maintenance-required limits of
several segment parameters and to enable or disable monitoring of out-of-specification limits.
All settings on this page are effective in commissioned mode only. A value of "0" disables real-
time monitoring of the limits.
Voltage: Segment voltage limits
Current: Segment current consumption
Unbalance: Segment unbalance against positive or negative pole
Noise: Segment noise level
100
Disabled: Segment is not used.
Non-commissioned: Segment operates in non-commissioned mode.
Commissioned: Segment operates in commissioned mode.