Pepperl+Fuchs HD2-DM-A Manual page 143

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Cabinet I/O
7.6.1
Configuring Typical Cabinet Management Applications Manually
Using Cooling Control
1.
Select an unused relay contact output and connect a cooling device (e.g., ventilator) to it.
2.
Select an unused on/off controller and configure it as follows:
Options: Not inverted
On level: Temperature level at which the output is supposed to be switched ON.
Off level: Temperature level at which the output is supposed to be switched OFF.
Input selection: Select the temperature input to be used as reference temperature.
3.
Configure the output source of the selected relay contact output to the selected on/off
controller.
4.
Configure measurement unit of selected temperature input.
Using Heater Control
1.
Select an unused relay output and connect a heater device to it.
142

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt-mb-dmaKt-mb-gt2ad.ffKt-mb-gt2ad.ff.io

Table of Contents