Pepperl+Fuchs HD2-DM-A Manual page 169

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Appendix
Parameter
FD_FAIL_AC-
TIVE
FD_OFF-
SPEC_AC-
TIVE
FD_-
MAINT_AC-
TIVE
FD_-
CHECK_AC-
TIVE
FD_FAIL_-
MAP
FD_OFF-
SPEC_MAP
FD_MAINT_-
MAP
FD_CHECK_-
MAP
FD_-
FAIL_MASK
FD_OFF-
SPEC_MASK
FD_-
MAINT_MAS
K
FD_-
CHECK_MAS
K
FD_-
FAIL_ALM
FD_OFF-
SPEC_ALM
FD_-
MAINT_ALM
FD_-
CHECK_ALM
FD_FAIL_PRI S, W, OOS
FD_OFF-
SPEC_PRI
FD_MAINT_-
PRI
FD_CHECK_-
PRI
168
Char.
Description
This parameter reflects the fault conditions that are detected as
active as selected for this category.
Since this parameter is a bit string, multiple conditions can be
issued.
See FD_FAIL_ACTIVE
See FD_FAIL_ACTIVE
See FD_FAIL_ACTIVE
S, W, OOS
This parameter maps conditions to be detected as active for
this alarm category. Thus, the same condition can be active in
all, some, or none of the 4 alarm categories.
S, W, OOS
See FD_FAIL_MAP
S, W, OOS
See FD_FAIL_MAP
S, W, OOS
See FD_FAIL_MAP
S, W, OOS
This parameter allows the user to suppress any single or multi-
ple conditions that are active in this category from being trans-
mitted to the host through the alarm parameter.
1 bit = 1 masks, i. e., inhibits the transmission of a condition
1 bit = 0 unmasks, i. e., enables transmission of a condition
S, W, OOS
See FD_FAIL_MASK
S, W, OOS
See FD_FAIL_MASK
S, W, OOS
See FD_FAIL_MASK
This parameter is primarily used to transmit a change in the
associated active conditions that are not masked, for this alarm
category to a host system.
See FD_FAIL_ALM
See FD_FAIL_ALM
See FD_FAIL_ALM
This parameter allows the user to specify the priority of this
alarm category.
S, W, OOS
See FD_FAIL_PRI
S, W, OOS
See FD_FAIL_PRI
S, W, OOS
See FD_FAIL_PRI