Pepperl+Fuchs HD2-DM-A Manual page 155

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Appendix
Parameter
Configuration data of nodes. The record is used 6 times (Z=1..6),18 nodes are configurable
(Y=1-18)
SEG-
MENT_(X)_D
EV_STAT-
IC_-
DATA_(Z)
Z=
1_3
4_6
7_9
10_12
13_15
16_18
154
Char.
Description
H1_SEGMENT_NONCOM_STATUS:
List of segment errors in non-commissioned mode:
Power supply A error
Power supply B error
Segment voltage high Out of Specification
Segment voltage high Good
Segment voltage low Good
Segment voltage low Out of Specification
Segment current high Good
Unbalance high Out of Specification
Unbalance high Good
Unbalance low Good
Unbalance low Out of Specification
Signal level high Out of Specification
Signal level high Good
Signal level low Good
Signal level low Out of Specification
Noise high Out of Specification
Noise high Good
Jitter high Out of Specification
Jitter high Good
Trunk surge protector alarm
H1_ERROR_RATE_ACT:
Error rate in actual history period – number of errors per
frames received.
H1_ERROR_RATE_LAST:
Error rate in previous history period – number of errors per
frames received
Record, W, S,
DEVICE_(Y)_ADDRESS:
OOS
Field device address:
0: Entry is not used (default)
1 ... 254: Entry is used
DEVICE_(Y)_TAG:
Field device tag
DEVICE_(Y)_SIGNAL_LEVEL_HI_HI_OOS:
Enable or disable segment maximum signal level High-Out-of-
Specification limit
DEVICE_(Y)_SIGNAL_LEVEL_HI_MR:
Segment maximum signal level High-Maintenance-Required
limit
0 mV: Disabled
100 mV ... 2200 mV: Enabled

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt-mb-dmaKt-mb-gt2ad.ffKt-mb-gt2ad.ff.io

Table of Contents