Pepperl+Fuchs HD2-DM-A Manual page 187

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Appendix
ID
267
268
269
270
186
Phenomenon
A device coupler "Out of
specification" alarm is
detected. Check Coupler
LEDs for the alarm cause.
A device coupler "Mainte-
nance required" alarm is
detected
A device coupler "Out of
specification" alarm is
detected for one device
A device coupler "Out of
specification" alarm is
detected and devices are
missing compared to com-
missioning
Cause(s)
Spur short circuit
An ELS or a surge protec-
tor sends an alarm. Device
coupler LED should blink
three times
ELS sends alarm. The
device coupler LED should
blink three times
The spurs of missing
devices or an empty spur
shows bad current
changes
The maximum power rating
of the device coupler is
exceeded
An empty spur is short cir-
cuited or shows bad cur-
rent changes
A diagnostic value exceeds
defined value. The device
coupler LED should blink
two times
A diagnostic value exceeds
defined value. The device
coupler LED should blink
one time
An ELS or a surge protec-
tor sends an alarm. Device
coupler LED should blink
three times
A diagnostic value exceeds
defined value. The device
coupler LED should blink
two times
Spur short circuit
The spurs of missing
devices or an empty spur
shows bad current
changes
The maximum power rating
of the device coupler is
exceeded
Action(s)
Check spur of the missing
device
Check device sending the
alarm and check any ELS
and surge protectors con-
nected to it
Check ELS of the device
coupler with active alarms
Check cable connections
and devices at the affected
spur
Reduce power consump-
tion of devices connected
to the device coupler
Check empty spurs of the
corresponding device cou-
pler
Check the device coupler
manual for details
Check device coupler
manual for details
Check device sending the
alarm and check any ELS
and surge protectors con-
nected to it
Check the device coupler
manual for details
Check spur of the missing
device
Check cable connections
and devices at the affected
spur
Reduce power consump-
tion of devices connected
to the device coupler

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt-mb-dmaKt-mb-gt2ad.ffKt-mb-gt2ad.ff.io

Table of Contents