Pepperl+Fuchs HD2-DM-A Manual page 43

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
Hardware Installation
For the FDS/OPC integration, up to 125 DGW or 1 000 ADMs (whichever maximum is reached
first) are supported for a single FDS server installation. For the FOUNDATION Fieldbus integra-
tion, this limit does not apply because every DGW is a single FF-H1 field device without any
connection to the other gateways.
Required Hardware Components
Hardware Component
KT-MB-GT2AD.FF
or
KT-MB-GT2AD.FF.IO
KT-MB-DMA
4.2.1
Installing the Diagnostic Bus
The maximum length of the diagnoastic bus channel is 30 m.
Installing the Diagnostic Bus
1.
In order to connect the diagnostic gateway to the FieldConnex
2.
In order to connect the Power Hubs with each other, use a 4-wire cable or the optional ACC-
MB-HDC link cable.
3.
Use shielded wires for the diagnostic bus in EMC-sensitive areas. Connect the cable shield to
the grounding terminal of the gateway motherboard.
4.
The principal way of connecting stand-alone kits to each other and to the diagnostic gateway is
shown in the figure below.
5.
The terminals used at the diagnostic gateway depends on the kit used.
KT-MB-GT2AD.FF:see chapter 3.3.1
KT-MB-GT2AD.FF.IO: see chapter 3.4.1
Description
Kit comprising the following hardware components:
HD2-GT-2AD.FF.IO: Diagnostic gateway
MB-FB-GT.AD.FF / MB-FB-GT.AD.FF.IO: Motherboard for
diagnostic gateway / I/O motherboard for diagnostic gate-
way
Kit comprising the following hardware components:
HD2-DM-A: Advanced diagnostic module
MB-FB-DM: Stand-alone motherboard for advanced diag-
nostic module
Channel 2
PRI
PWR
SEC
PWR
Fieldbus
Diagnostic
Module
Extended
Version
Seg1
Seg2
Seg3
Seg4
Channel 1
Diagnostic Modules
Diagnostic Bus Line
®
Power Hub, use a 4-line wire.
ACC-MB-HDC link cable
+
-
PRI
PRI
PWR
PWR
SEC
SEC
PWR
PWR
Alarm
Fieldbus
Fieldbus
Diagnostic
Diagnostic
Module
Module
Extended
Extended
Version
Version
Seg1
Seg1
Seg2
Seg2
Seg3
Seg3
Seg4
Seg4
MOTHERBOARD
last motherboard
+
-
LAST
LINK
This is used to
maintain loop
continuity at the
43