Advanced Diagnostics
Appendix
Channel
Number
12
13
101
102
103
104
105
201
8.4
HD2-GT-2AD.FF.IO FF Field Diagnostic Conditions
Bit
0
1
2
3
4
5
Allowed for
Data Type
FB
8 x DS-66
MDI
8 x DS-66
MDI
8 x DS-66
MDI
8 x DS-66
MDI
8 x DS-65
MAI
8 x DS-65
MDO
1x DS-66
DI, MDI
1x DS-66
DI
Name
Description
Check Function
Actual block mode does not match nor-
mal mode and normal mode is unequal
to OOS.
ADM Maintenance
Any ADM system or segment where the
Required
corresponding ADM_TB with target
mode "AUTO" has a status of "Mainte-
nance Required".
ADM Out of Specifi-
Any ADM system or segment where the
cation
corresponding ADM_TB with target
mode "AUTO" has a status of "Out of
Specification".
ADM Non Commis-
Any ADM where the corresponding
sioned
ADM_TB with target mode "AUTO" has
non-commissioned segments.
ADM Fail
Any ADM system or segment where the
corresponding ADM_TB with target
mode "AUTO" has a status of "Fail".
ADM Not Con-
Any ADM_TB with target mode "AUTO"
nected
where no corresponding ADM can be
found on any diagnostic bus.
Content
Value: Status of ADMs with Address 1 ... 8 encoded
like channel 11
Status:
•
Bad (Out of Service) if corresponding ADM_TBs
is in Out-of-Service mode
•
Good (NC) in all other cases
Same as channel 12 but for ADMs 9 ... 16
Input value and status of binary inputs 1 ... 8
1 ... 4: Value and status of on/off controller 1 ... 4
5 ... 8: Value 0, status "Bad"
1: Value and status of temperature input 1
2: Value and status of temperature input 2
3: Value and status of board temperature
4: Value and status of board humidity
5: Value and status of frequency input 1
6: Value and status of frequency input 2
7, 8: Value 0, status "Bad"
1: Relay contact output 1 (output source of relay con-
tact output 1 must be set to "FF channel")
2: Relay contact output 2 (output source of relay con-
tact output 2 must be set to "FF channel")
3: Buzzer (output source of buzzer must be set to
"FF channel")
4: Common alarm output (output source of common
alarm output must be set to "FF channel")
5 ... 8: Ignored
Status of BINARY_INPUT_1 ... BINARY_INPUT_8
as bits of the U8. If channel is used for MDI, only
OUT_1 is used!
Field diagnostic of resource block
Default Mapping
Check function
Maintenance
Required
Offspec
Check function
Fail
Fail
171