Advanced Diagnostics
Cabinet I/O
High Maintenance Required: If the currently measured frequency value is higher than the
High-Maintenance–Required limit, the field diagnostics IO_TB–Maintenance–Required
condition is triggered.
Low Maintenance Required: Like High Maintenance Required, but for measured fre-
quency lower than the Low–Maintenance–Required value.
Low Maintenance Required: Like High Maintenance Required, but for measured fre-
quency lower than the Low–Maintenance–Required value.
Hysteresis: In order to avoid the flickering of diagnostics, a hysteresis value can be config-
ured.
7.2.2
Binary Inputs
Lead breakage and short circuit detection can be enabled and disabled.
Invert: Invert binary input value.
Use fault state: If an error is detected, the input status remains "GOOD" instead of becom-
ing "BAD". Depending on the setting of "Fault state to value", the input value remains on
the last "GOOD" value or changes to the fault state value.
Fault state to value: If enabled, the input value changes to the value of the "Fault state" bit
when an error is detected instead of remaining on the last "GOOD" value.
Fault state: Fault state value, used with "Fault state to value".
Field Diag Out Of Specification: If this option is set, a logical 1 at the binary input triggers
an IO_TB-Out-of-Specification condition.
Field Diag Maintenance Required: If this option is set, a logical 1 at the binary input trig-
gers an IO_TB-Maintenance-Required condition.
7.2.3
Temperature/Binary Inputs
Lead breakage and short circuit detection can be enabled and disabled.
Use as binary input: Use input as binary input instead of temperature input.
The following settings are only used in binary mode:
Invert: Invert binary input value.
Use fault state: If an error is detected, the input status remains "GOOD" instead of becom-
ing "BAD". Depending on the setting of "Fault state to value", the input value remains on
the last "GOOD" value or changes to the fault state value.
Fault state to value: If enabled, the input value changes to the value of the "Fault state" bit
when an error is detected instead of remaining on the last "GOOD" value.
Fault state: Fault state value, used with "Fault state to value".
Field Diag Out Of Specification: If this option is set, a logical 1 at the binary input triggers
an IO_TB-Out-of-Specification condition.
Field Diag Maintenance Required: If this option is set, a logical 1 at the binary input trig-
gers an IO_TB-Maintenance-Required condition.
The following settings are only used in temperature mode:
High Out of Specification: If the currently measured temperature value is higher than
High-Out-of-Specification limit, the field diagnostics IO_TB-Out-of-Specification condition
is triggered.
High Maintenance Required: If the currently measured temperature value is higher than
High-Maintenance-Required limit, the field diagnostics IO_TB-Maintenance-Required
condition is triggered.
Low Maintenance Required: Like High Maintenance Required, but for measured tempera-
ture lower than Low-Maintenance-Required value.