Advertisement

Advanced Diagnostics
FOUNDATION Fieldbus Integration
2.
Right-click on control network and choose Export.
3.
Enter the file name and save the file.
During import, the tags are assigned to the ADM transducer blocks in the following way:
FF-H1 cards are assigned from the lowest to the highest card number to the transducer blocks.
Since a DeltaV H1 card has 2 segments, and an ADM has 4 segments, the cards are assigned
using the following algorithm:
Check if 4 continuously addressed Emerson cards with the addresses 1 ... 4, 5 ... 8, (and
so on) contain non-redundant cards.
6.8.9.2
Export Tags from Honeywell Experion
Exporting Tag from Honeywell Experion
1.
On Experion Server, open configuration studio and select Control Strategy > Configure
process control strategies to open the control builder.
2.
Right-click on a root in the project assignment window. Choose Export.
3.
Select at least all FIM4, FIM8, Fieldbus Devices and Templates for Fieldbus Devices.
Choose a directory to export to, and click Export.. Typically, it is the best way to select all and
export.
FIMs are assigned from the lowest to the highest device index to the ADM transducer
blocks. Any FIM8 allocates to consecutive ADM transducer blocks.
130
If the block contains at least 1 non-redundant card, the card addresses 1 + 2, 3 + 4,
(and so on) are combined at an ADM. If redundant cards are in this block, the ADM
segments reserved for the redundant card remain unused.
If the block only contains redundant cards, the cards with the addresses 1 ... 4,
5 ... 8, (and so on) are mapped to 1 ADM. This is possible because in a redundant
system, even address numbers are not used.