Advanced Diagnostics
Appendix
Parameter
SEG-
MENT_(X)_D
YNAMIC
152
Char.
Description
H1_SIGNAL_LEVEL_HI_MR:
Segment maximum signal level High-Maintenance-Required
limit.
0 mV: Disabled
100 mV ... 2200 mV: Enabled
H1_SIGNAL_LEVEL_LO_MR:
Segment minimum signal level Low-Maintenance-Required
limit.
0 mV: Disabled
100 mV ... 2200 mV: Enabled
H1_SIGNAL_LEVEL_LO_LO_OOS:
Enable or disable segment minimum signal level Low-Out-of-
Specification limit.
H1_NOISE_HI_HI_OOS:
Enable or disable segment noise level High-Out-of-Specifica-
tion limit.
H1_NOISE_HI_MR:
Segment noise level low maintenance required limit:
0 mV: Disabled
25 mV ... 1000 mV: Enabled
H1_JITTER_HI_HI_OOS:
Enable or disable segment jitter level High-Out-of-Specifica-
tion limit.
H1_JITTER_HI_MR:
Segment jitter High-Maintenance-Required limit:
0 µS: Disabled
0.5 ... 7 µS: Enabled
H1_TRUNK_ALARM:
Enable or disable trunk surge protector alarm.
IGNORE_TOPOLOGY_SETTINGS:
Ignore or use the following topology settings.
POWERSUPPLY_TYPE:
Segment power supply type.
COUPLER_TYPE:
Device coupler type used on segment.
COUPLER_COUNT:
Number of device couplers on segment.
TRUNK_LENGTH:
Segment trunk length.
TRUNK_CABLE_TYPE:
Segment trunk type.
TOPO_OPTIONS:
Topology options:
Enable or disable monitoring of surge protector status.
Record
H1_COMMUNICATION_ACTIVE:
Communication is detected on segment.
H1_NUM_ACTIVE_DEVICES:
Number of detected field devices.
H1_U:
Segment voltage
H1_I:
Segment current (not available on some motherboards).