Advanced Diagnostics
Hardware Installation
4
Hardware Installation
4.1
Power Hub and Advanced Diagnostic Module
In order to provide advanced diagnostics for FieldConnex
mounted on the Power Hubs and are connected to each other and to the diagnostic gateway
(DGW) via a dedicated diagnostic bus. The figure below shows an installation example.
KT-MB-GT2AD.FF*
PCS
connection
MB-FB-GTAD.FF*
Figure 4.1
System topology with diagnostic gateway, Power Hubs and advanced diagnostic modules
The DGW provides 2 diagnostic bus channels. Depending on the PCS connection used you
can connect either of the following:
FDS/OPC: 31 Power Hub motherboards (for each channel) / 62 Power Hub motherboards
(for both channels)
FOUNDATION Fieldbus: 8 Power Hub motherboards (for each channel) / 16 Power Hub
motherboards (for both channels)
Note
For best performance, use the same number of Power Hub motherboards on each diagnostic
bus channel.
For the FDS/OPC integration, up to 125 DGWs or 1 000 ADMs (whichever maximum is
reached first) are supported for a single FDS server installation. For the FOUNDATION Field-
bus integration, this limit does not apply because every DGW is a single FF-H1 field device
without any connection to the other gateways.