Advanced Diagnostics
Appendix
Parameter
SEG-
MENT_(X)_S
TATIC
Char.
Description
EXPERT_MSG_(N):
Expert message. For detailed explanation, .
Record, W, S,
H1_TAG:
OOS
Segment tag
H1_MODE:
Segment mode
•
Disabled
•
Non commissioned (default)
•
Commissioned
PS_MODULE_SUPERVISION:
Enables diagnostics of power supply modules. If enabled,
segment power supply errors are reported (module missing,
module failure).
•
Supervise power supply A.
•
Supervise power supply B (on redundant boards).
H1_U_HI_HI_OOS:
Enable or disable segment voltage High-Out-of-Specification
limit.
H1_U_HI_MR:
Segment voltage high maintenance required limit.
•
0: Disabled
•
9 ... 32 V: Enabled
H1_U_LO_MR:
Segment voltage Low-Maintenance-Required limit.
•
0: Disabled
•
9 ... 32 V: Enabled
H1_U_LO_LO_OOS:
Enable or disable segment voltage Low-Out-of-Specification
limit.
H1_I_HI_MR:
Segment current High-Maintenance-Required limit.
•
0: Disabled
•
1 ... 6500 mA: Enabled
H1_I_LO_MR:
Segment current Low-Maintenance-Required limit.
•
0: Disabled
•
1 ... 6500 mA: Enabled
H1_UNBALANCE_HI_HI_OOS:
Enable or disable segment unbalance High-Out-of-Specifica-
tion limit.
H1_UNBALANCE_HI_MR:
Segment unbalance High-Maintenance-Required limit.
•
0: Disabled
•
-100% ... 100%: Enabled
H1_UNBALANCE_LO_MR:
Segment unbalance Low-Maintenance-Required limit.
•
0: Disabled
•
-100% ... 100%: Enabled
H1_UNBALANCE_LO_LO_OOS:
Enable or disable segment unbalance Low-Out-of-Specifica-
tion limit.
H1_SIGNAL_LEVEL_HI_HI_OOS:
Enable or disable segment maximum signal level High-Out-of-
Specification limit.
151