Pepperl+Fuchs HD2-DM-A Manual page 103

Advanced diagnostics
Hide thumbs Also See for HD2-DM-A:
Table of Contents

Advertisement

Advanced Diagnostics
FOUNDATION Fieldbus Integration
2. Topology information: Using the topology information that can be entered here, the expert
system can refine its diagnostics of the current segment measurement information. This is
useful in step 4.
3. Field device tagging: In this step, tags for the field devices can be assigned in either of the
following 2 ways:
4. Show actual segment diagnostics based on topology information provided in step 2. This
is the last possibility make any corrections on the segment before the actual commission-
ing run. Ensure that all problems on the segment are fixed before proceeding with next
step of the wizard.
5. The actual commissioning is running automatically and takes several seconds to collect
enough measurement data. The commissioning wizard configures the alarm limits auto-
matically based on the measured data.
6. Presentation of commissioning result. You can review and edit the adjustments of the
maintenance limits that the commissioning algorithm set automatically. The segment is
now running in commissioned mode.
Segment Commissioning (Simple Mode)
Method also supported by DD4. Only step 5 of the commissioning wizard is executed.
Segment Tag Import (Simple Mode)
Method also supported by DD4. This method can import the tags of most devices on the seg-
ment automatically. This method is used most often except for the host itself. In order to use this
wizard, it is necessary to disconnect the host from and reconnect the host to the affected seg-
ment. Follow the instructions of the wizard.
Identify Diagnostic Module (Flash LEDs)
Method also supported by DD4. This method causes the HD2-DM-A module to have all LEDs
flashing for identification purpose.
ADM Firmware Update
The DGW-FF has an ADM firmware built in. This method can be used to update an ADM to any
firmware compatible with the DGW-FF.
6.6
Installation of DGW-FF Device Type Managers with PACTware
Installing DGW-FF Device Type Managers with PACTware
Ensure you downloaded the software bundle that includes the DGW-FF device type manager
(DTM) and all its tools and accessories, e.g., PACTware
uration tool from www.pepperl-fuchs.com. In order to install the FieldConnex
proceed as follows:
1.
Extract the software bundle to a local directory.
2.
Go to the directory that includes the extracted files and run autorun.exe to start the installation
wizard.
3.
Select the software components you want to install and choose Install selected
application(s).
We recommend that you install all components.
Entering tags manually in a grid.
Using a tag import wizard: The tag import wizard can import the tags of most devices
on the segment automatically. This method is used most often except for the host
itself. In order to use this wizard, it is necessary to disconnect the host from and
reconnect the host to the affected segment. Follow the instructions of the wizard.
TM
TM
, and the diagnostic gateway config-
®
DGW-FF DTMs,
TM
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt-mb-dmaKt-mb-gt2ad.ffKt-mb-gt2ad.ff.io

Table of Contents