Physical installation
............................................................................................................................................................................................................................................................
The secondary ground would consist of a 12 AWG wire from the UL (Green M5
Screw) safety ground on the lower left side of the rear of the shelf to the bayframe
(where the bayframe has been scraped clean of paint and treated with no-ox) or
directly to the office ground. See
Figure 2-7 Safety ground screw.
........................................................................................................................................................................................................................
9
Mount the ESD Jack Stud on the rear of the bayframe where it will be accessible when
accessing the rear of the shelf.
........................................................................................................................................................................................................................
10
If fiber spools are to be used, attach the spools to the Alcatel-Lucent 1665 DMXtend using
the Fiber Spool Bracket Kit drawing 848949152. Attach the bracket to the shelf first and
then the top fiber spool to the bracket. The lower fiber spool will need to overlap the top
spool to snap into place. Run the excess fiber per office practices around the spools to
minimize the bend radius. See
........................................................................................................................................................................................................................
11
If Alcatel-Lucent fiber ducts are used, see
speed fibers are to be run in the duct closest to the shelf for both left and right ducts. The
next two ducts away from the shelf are for low-speed fibers.
............................................................................................................................................................................................................................................................
2 - 1 2
Figure 2-7, "Safety ground screw." (p.
Figure 2-8, "Fiber spools" (p.
Figure 2-8, "Fiber spools" (p.
2-12).
2-13).
2-13). All high-
Alcatel-Lucent 1665 DMXtend R10.0
365-372-327R10.0 Issue 1
January 2013