Physical installation
............................................................................................................................................................................................................................................................
Fiber duct
This section will describe how to install an optional fiber duct.
Note:
accommodate the duct below the existing Alcatel-Lucent 1665 DMXtend. Use the
Assembly Fiber Duct kit drawing 848949152 to attach the duct to the Alcatel-Lucent
1665 DMXtend. See
Figure 2-6 Fiber duct mounting
........................................................................................................................................................................................................................
8
Position the Alcatel-Lucent 1665 DMXtend shelf in the frame and secure the shelf to the
frame using the thread-forming screws included with the shelf (3 screws per side). Tighten
the screws to 21 in.-lb. (minimum)/30 in.-lb. (maximum).
Note:
rear of the chassis as installed. It is labeled "FILT BLK" and the two positions are
"ENABLE" and "DISABLE." The fan ships with the jumper in the disable position
which prevents the filter alarm from working. To enable the filter alarm, move the
jumper to the "ENABLE" position. This is the only jumper on the board. The OSP
cabinet must be engineered so that the Alcatel-Lucent 1665 DMXtend does not
impede air flow to other equipment in the cabinet. The OSP cabinet must be
engineered to provide a two inch open space on the left and right sides of the Alcatel-
Lucent 1665 DMXtend for air flow. Mounting frame and flanges may intrude on this
space.
Note:
shelf to ensure a solid ground connection from the bay to the shelf.
Note:
paint indicate that the material is not always removed cleanly using the thread forming
screws and can create a poor ground, thus we recommend a secondary ground be used.
............................................................................................................................................................................................................................................................
Alcatel-Lucent 1665 DMXtend R10.0
365-372-327R10.0 Issue 1
January 2013
If a fiber duct is being used to diversify fiber, a 1-inch space is required to
Figure 2-6, "Fiber duct mounting" (p.
There is a jumper on the fan controller board, at the corner closest to the top-
Be sure to mount the shelf using the thread-forming screws provided with the
For bays that use power coat paint e.g., most 19" bays, studies on that type of
2-11).