Cable and fiber installation
........................................................................................................................................................................
Steps
................................................................................................................................................
1
See the engineering job specification. Determine the function slot where the pack will be
inserted. The OC-3/OC-12/OC-48 pack can be inserted into either the D or G function
slots.
................................................................................................................................................
2
Label the optical fiber cables, indicating bay, shelf, function group, pack, and direction
(IN or OUT).
................................................................................................................................................
3
Route optical fiber cables from the interconnecting equipment into the left side of the
Alcatel-Lucent 1665 DMXtend and into the OC-3/OC-12/OC-48 optical ports. See
Figure 3-19, "Optical fiber routing" (p.
................................................................................................................................................
4
Place the optical fiber cables in a protective tube or channel.
................................................................................................................................................
5
Check off the appropriate box in the
E
O
N D
........................................................................................................................................................

100/1000BASE-X optical fiber cable installation

Description
This section describes how to route the optical fiber cables from the interconnecting
equipment (for example, an LGX
LNW63, LNW64, LNW74, LNW87, and LNW170 Ethernet circuit packs.
Single-mode fiber is required for LNW170 (1000Base-F ports).
Note:
placed in a protective tube or channel, such as PVC tubing, or PANDUIT cable
channel, when running the cable from the Alcatel-Lucent 1665 DMXtend to the cable
rack. The fibers should be placed in the cable rack in a protective channel with nothing
on top of them. Cable ties should NOT be used with the optical fiber cables.
........................................................................................................................................................................
3 - 6 2
S
F
T E P S
The optical fiber cable is fragile and must be protected. The fibers should be
3-60).
Table I-2, Installation
®
optical fiber distributing frame) to the optical ports on
checklist.
Alcatel-Lucent 1665 DMXtend R10.0
365-372-327R10.0 Issue 1